| Conductor | Insulation | |
| Stranded bare copper (Class 2) Acc. to VDE 0276-620 | XLPE DIX8 | |
| Electrical Field Control | Screen | |
| Inner and outer semiconducting layer (triple extrusion) | Copper wires + counter helix | |
| Sheath | Electrical | |
| Outer sheath: polyethylene DMP2 (longitudinally watertight) Colour: black | Nominal voltage: 18/30 kV Max. operating voltage in three-phase systems: 36 kV Test voltage: 63 kV Partial discharge: 2 pC | |
| Temperature | Bending Radius | |
| Operating temperature range, fixed: +70 °C Operating temperature range, flex: -20 °C to +70 °C Max. temperature at conductor: +90 °C | Bending radius, fixed: 15 x Ø | |
| Approval | ||
| UV-resistant: yes For outdoor use: yes |