| Conductor | Insulation | |
| Flexible tinned copper (Class 5) Acc. to VDE 0250 T. 812 | Rubber 3Gl3 | |
| Core Identification | Sheath | |
| Colours acc. to VDE 0293 (HD 308) | Outer sheath: rubber 5GM5 Colour: yellow | |
| Electrical | Temperature | |
| Nominal voltage: 0,6/1 kV Test voltage: 3 kV | Operating temperature range, fixed: -40 °C to +80 °C Operating temperature range, flex: -25 °C to +60 °C Max. temperature at conductor: +90 °C | |
| Bending Radius | Flame | |
| Bending radius, fixed (<12mm): 3 x Ø Bending radius, fixed (>12mm): 4 x Ø Bending radius, flex (<12mm): 5 x Ø Bending radius, flex (>12mm): 6 x Ø | VDE 0482-332-1-2 / IEC 60332-1-2 | |
| Approval | ||
| Oil-resistant: EN 60811-404 UV-resistant: yes For outdoor use: yes |