| Conductor | Insulation | |
| Stranded bare copper (Class 2) Acc. to DIN VDE 0295 / IEC 60228 | XLPE Acc. to EN 50290-2-29 | |
| Core Identification | Stranding | |
| Pairs: white – black Triads: white – black – red Quads: white – black – red – grey More: white cores with consecutive black numbers | Cores stranded in pairs / triads / quads, cores stranded in cable elements with optimal lay lengths; cable elements are stranded with optimal lay lengths | |
| Screen | Armour | |
| AL/PET tape over tinned copper stranded drain wire (7×0,3mm) | Single layer of galvanized round steel wires (GSWA) Acc. to EN 10257-1 | |
| Sheath | Electrical | |
| Inner sheath: PVC acc. to EN 50290-2-22 Outer sheath: PVC acc. to EN 50290-2-22 Colour: black RAL 9005 or blue RAL 5015 | Nominal voltage: 300 V Test voltage (core/core – core/screen): 1500 V Insulation resistance: > 5000 MΩxkm Mutual capacitance: max. 150 pF/km Inductance: max. 1 mH/km L/R (ratio): – 0,5 mm² < 25 µH/Ω – 0,75 mm² < 25 µH/Ω – 1 mm² < 25 µH/Ω – 1,5 mm² < 40 µH/Ω – 2,5 mm² < 60 µH/Ω | |
| Temperature | Bending Radius | |
| Operating temperature range, fixed: -30 °C to +90 °C Operating temperature range, flex: -5 °C to +50 °C | Bending radius, fixed: 10 x Ø | |
| Flame | Approval | |
| DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2 / DIN VDE 0482-332-3-22 / DIN EN 60332-3-22 / IEC 60332-3-22 (Cat. A, 40 min) | Oil-resistant: ICEA S-73-532 / NEMA WC 57 UV-resistant: UL 1581 sec. 1200 Outdoor use: yes |