| Conductor | Insulation | |
| Stranded bare copper (Class 2) Acc. to VDE 0276-620 | XLPE DIX8 | |
| Electrical Field Control | Screen | |
| Inner and outer semiconducting layer (triple extrusion) | Copper wires + counter helix one each core | |
| Sheath | Electrical | |
| Outer sheath: PVC DMV6 Colour: red | Nominal voltage: 6/10 kV Max. operating voltage in three-phase systems: 12 kV Test voltage: 21 kV Partial discharge: 2 pC | |
| Temperature | Bending Radius | |
| Operating temperature range, fixed: +70 °C Operating temperature range, flex: -5 °C to +70 °C Max. temperature at conductor: +90 °C | Bending radius, fixed: 15 x Ø | |
| Flame | Approval | |
| VDE 0482-332-1-2 / IEC 60332-1-2 | For outdoor use: yes |